Data center load calculator
Size power and cooling for a rack or a room
Enter what you are deploying. This returns IT load, cooling in tons and BTU/hr, UPS capacity at your redundancy target, and a circuit check against the 80% continuous-load derate — with the assumptions shown so you can defend the numbers. Free, vendor-neutral, no signup.
Results
v1.1.0Sized to 2 circuits per rack, the minimum that keeps each one under 80%.
Perimeter cooling with containment
Hot or cold aisle containment becomes necessary. This band covers most enterprise rooms — Uptime put modal density at 11 kW in 2026, up from 9 kW the year before.
Checks
Nothing flagged. The configuration sits inside the electrical and thermal limits this tool checks.
Every formula, constant, and standard behind these numbers is published on the methodology page.